Modbus Crawler

Generic Modbus crawler that reads and writes registers according to device and register spec.

Author: Christian Seitl, christian.seitl@ait.ac.at

Registers are specified either in a pandas data frame or a csv-file. The columns are:

  • Register_start: start address of modbus read register command.
  • Register_end: end address of modbus read register command Not necessary anymore. Will be calculated automatically from data_type size.
  • Register_type: either i for input register, h for holding register, c for coil and d for discrete input.
  • Data_type: Data type of variable. Depending on type the variable is kept in 1, 2 or 4 16-bit registers.
    • currently supported: BOOL, INT16, UINT16, INT32, UINT32, INT64, UINT64, SINGLE (float), DOUBLE (float), HALF ( precision float).
    • Note: Word and byte order can be set in the constructor.
    • Note: BOOL is required for coil and discrete input registers.
    • Note: Only works on block level, i.e. all registers in a block must have the same data type. First register defines the block data type.
  • Name of variable.
  • Unit of variable (optional, not used in the code).
  • Scaling of variable (optional column, default None): Often fixed point values are stored in a scaled INT register, which is an easy way to store comma values in one single register
    • e.g. U_L1 = 23174 and Scaling = 0.01 which lead to U_L1 = 231.74 .
    • When using 'scaling = 1' on an int register, the value will be returned as a float.
    • If float uses 'scaling = 1' the value will not be changed to avoid floating point errors.
    • Any other scaling values will return a float.
  • Used (optional column, default True): If False, the block will be ignored.
    • Note: Only works on block level, i.e. all registers in a block must have the same value. First register defines the block value.
  • Unit_ID (optional column, default 1): Unit ID (Slave ID) when sending the read register command.
    • Note: Only works on block level, i.e. all registers in a block must have the same Unit_ID. First register defines the block Unit_ID.
  • description (optional column, not used int the code): Description of the variable.
  • mode (optional column, default 'r'): If the variable should be read ('r') or written ('w') or both ('rw').
    • Note: Only works on block level, i.e. all registers in a block must have the same mode. First register defines the block mode.

Example:

Register_start Register_end Register_type Data_type Name Unit Scaling
100 100 i INT16 I_L1 A 0.01
110 111 i SINGLE f Hz 1
200 205 i SINGLE U_L1 V 1
x x i SINGLE U_L2 V 1
x x i SINGLE U_L3 V 1
  • Registers are read in blocks. A block is defined from Register_start until the line above the next number in the column Register_start.
  • First line will read one register (100), decode the bytes as INT16 multiple with 0.01
  • Second line will read two registers (110 to 11), decode as single float
  • Third line will read six registers (200 to 205), decode the first two as single, store into U_L1, the next two into U_L2 and so on
  • This is done to reduce number of read commands which saves time and traffic (reading 50 registers at once vs. 50 times one register)
  • Some Modbus devices force you to read a list of single floats pairwise (e.g. some SMA inverters). Then the entries would be 200-201, 202-203, 204-205
    • Note: due to Modbus protocol definition, only 123 registers can read at once
  • Header row is not case-sensitive and can also be in snake-case, e.g.:
    • datatype -> datatype
    • DataType -> datatype
    • DATATYPE -> datatype
    • data_type -> datatype
  • Entries in columns Register_type and Data_type are case-insensitive too, but don't use snake case
  • Strings are supported to read and write with the data_type: stringX where X is the number of registers the string uses which is always half the size of the string bytes because one register has 2 bytes. When writing the string will be padded with spaces to the right to fill the registers. Up to 128 registers can be read at once (256 bytes).
    • e.g. string10 reads 10 characters from the registers striping white spaces at the start or end
  • input_data_validation.py defines some aliases for register and data types, e.g. (subset)
    • int: int16, short
    • uint: uint16, ushort
    • dint: int32, long
    • float: float32, single, real and
    • i: 4, 0x04, ir, inputregister, inputreg
    • h: 3, 0x03, hr, holdingregister, holdingreg
  • Registers can be written to individually addressable by id or name.

API

register_spec_df = pd.read_csv("register_spec.csv")

modbus_device = ModbusTcpDevice("localhost", 502, byteorder=Endian.BIG, wordorder=Endian.BIG, auto_connect=True,
                                registers_spec_df=register_spec_df, register_specs_file_name=None)

modbus_device.connect()
registers = modbus_device.read_registers_as_dict()
modbus_device.disconnect()

Functions in ModbusTcpDevice:

def connect(self):
    """Connects to the Modbus device."""


def disconnect(self):
    """Disconnects from the Modbus device."""


@property
def connected(self) -> bool:
    """Returns True if connected to the Modbus device."""


def read_registers_as_dict(self) -> dict[str, float]:
    """Reads all registers and returns them as dictionary."""


def read_registers(self) -> list[ModbusRegister]:
    """Reads all registers with mode `r` or `rw` and returns them as list of ModbusRegister objects."""


def read_register(self, register: str | int) -> ModbusRegister:
    """Reads a single register with mode `r` or `rw` and returns it as ModbusRegister object."""


def write_register(self, register: str | int, value):
    """Writes a single register."""