diff --git a/PowerWalker/PowerWalker__VFI_2000_CRM_LCD__nutdrv_qx__2.8.1__01.dev b/PowerWalker/PowerWalker__VFI_2000_CRM_LCD__nutdrv_qx__2.8.1__01.dev new file mode 100644 index 0000000..79a9ff8 --- /dev/null +++ b/PowerWalker/PowerWalker__VFI_2000_CRM_LCD__nutdrv_qx__2.8.1__01.dev @@ -0,0 +1,165 @@ +# Please add if relevant: DEVICE:URL:REPORT: https://github.com/networkupstools/nut/issues/3333 +# Please add if relevant: DEVICE:URL:VENDOR: https://powerwalker.com/de/produkt/10122001/ + +# DEVICE:COMMENT: +# Device dump generated by dump.sh on Sat, 28 Feb 2026 14:42:18 +0000 +# PowerWalker VFI 2000 CRM LCD +# DEVICE:EOC + +# :; upsc powerwalker +battery.charge: 98 +battery.energysave: no +battery.packs: 1 +battery.protection: yes +battery.runtime: 1920 +battery.voltage: 054.5 +battery.voltage.high: 52.00 +battery.voltage.low: 41.60 +battery.voltage.nominal: 48.0 +device.model: WPHVR2K0 +device.type: ups +driver.debug: 0 +driver.flag.allow_killpower: 0 +driver.name: nutdrv_qx +driver.parameter.pollfreq: 30 +driver.parameter.pollinterval: 1 +driver.parameter.port: auto +driver.parameter.productid: 5161 +driver.parameter.synchronous: auto +driver.parameter.vendorid: 0665 +driver.state: quiet +driver.version: 2.8.1 +driver.version.data: Voltronic 0.08 +driver.version.internal: 0.36 +driver.version.usb: libusb-1.0.27 (API: 0x100010a) +input.frequency: 50.0 +input.frequency.high: 53.0 +input.frequency.low: 47.0 +input.frequency.nominal: 50.0 +input.phases: 1 +input.transfer.high: 242 +input.transfer.high.max: 254 +input.transfer.high.min: 237 +input.transfer.low: 218 +input.transfer.low.max: 223 +input.transfer.low.min: 206 +input.voltage: 236.2 +input.voltage.nominal: 230.0 +output.current: 1.6 +output.current.nominal: 8 +output.frequency: 50.0 +output.frequency.nominal: 50.0 +output.phases: 1 +output.power.maximum.percent: 19 +output.power.minimum.percent: 21 +output.powerfactor: 0.8 +output.voltage: 230.2 +output.voltage.nominal: 230.0 +ups.beeper.status: enabled +ups.delay.shutdown: 30 +ups.delay.start: 180 +ups.firmware: 01072.07 +ups.firmware.aux: P01 +ups.load: 22 +ups.power.nominal: 2000 +ups.productid: 5161 +ups.start.auto: yes +ups.start.battery: yes +ups.status: OL +ups.temperature: 27.7 +ups.type: online +ups.vendorid: 0665 + +# DEVICE:COMMENT-BLOCK:FIXME:UPSRW: powerwalker +# [battery.energysave] +# Switch off when running on battery and no/low load +# Type: ENUM NUMBER +# Option: "no" SELECTED +# Option: "yes" +# +# [battery.packs] +# Number of battery packs +# Type: RANGE NUMBER +# Option: "1-99" SELECTED +# +# [battery.protection] +# Prevent deep discharge of battery +# Type: ENUM NUMBER +# Option: "no" +# Option: "yes" SELECTED +# +# [driver.debug] +# Current debug verbosity level of the driver program +# Type: NUMBER +# Value: 0 +# +# [driver.flag.allow_killpower] +# Safety flip-switch to allow the driver daemon to send UPS shutdown command (accessible via driver.killpower) +# Type: NUMBER +# Value: 0 +# +# [input.frequency.high] +# Maximum input line frequency (Hz) +# Type: RANGE NUMBER +# Option: "53-60" SELECTED +# +# [input.frequency.low] +# Minimum input line frequency (Hz) +# Type: RANGE NUMBER +# Option: "40-47" SELECTED +# +# [input.transfer.high] +# High voltage transfer point (V) +# Type: RANGE NUMBER +# Option: "237-254" SELECTED +# +# [input.transfer.low] +# Low voltage transfer point (V) +# Type: RANGE NUMBER +# Option: "206-223" SELECTED +# +# [ups.delay.shutdown] +# Interval to wait after shutdown with delay command (seconds) +# Type: RANGE NUMBER +# Option: "12-5940" SELECTED +# +# [ups.delay.start] +# Interval to wait before (re)starting the load (seconds) +# Type: RANGE NUMBER +# Option: "0-599940" SELECTED +# +# [ups.start.auto] +# UPS starts when mains is (re)applied +# Type: ENUM NUMBER +# Option: "no" +# Option: "yes" SELECTED +# +# [ups.start.battery] +# Allow to start UPS from battery +# Type: ENUM NUMBER +# Option: "no" +# Option: "yes" SELECTED +# DEVICE:EOC + +# DEVICE:COMMENT-BLOCK:FIXME:UPSCMD: powerwalker +# Instant commands supported on UPS [powerwalker]: +# +# beeper.disable - Disable the UPS beeper +# beeper.enable - Enable the UPS beeper +# beeper.toggle - Toggle the UPS beeper +# bypass.start - Put the UPS in bypass mode +# bypass.stop - Take the UPS out of bypass mode +# driver.killpower - Tell the driver daemon to initiate UPS shutdown; should be unlocked with driver.flag.allow_killpower option or variable setting +# driver.reload - Reload running driver configuration from the file system (only works for changes in some options) +# driver.reload-or-error - Reload running driver configuration from the file system (only works for changes in some options); return an error if something changed and could not be applied live (so the caller can restart it with new options) +# driver.reload-or-exit - Reload running driver configuration from the file system (only works for changes in some options); exit the running driver if something changed and could not be applied live (so service management framework can restart it with new options) +# load.off - Turn off the load immediately +# load.on - Turn on the load immediately +# shutdown.return - Turn off the load and return when power is back +# shutdown.stayoff - Turn off the load and remain off +# shutdown.stop - Stop a shutdown in progress +# test.battery.start - Start a battery test +# test.battery.start.deep - Start a deep battery test +# test.battery.start.quick - Start a quick battery test +# test.battery.stop - Stop the battery test +# DEVICE:EOC