Current Modbus function-code coverage for mbus-server.
| FC | Name | Feature Flag | Callback | Direction |
|---|---|---|---|---|
0x01 |
Read Coils | coils |
read_coils_request |
Read |
0x02 |
Read Discrete Inputs | discrete-inputs |
read_discrete_inputs_request |
Read |
0x03 |
Read Holding Registers | holding-registers |
read_multiple_holding_registers_request |
Read |
0x04 |
Read Input Registers | input-registers |
read_multiple_input_registers_request |
Read |
0x05 |
Write Single Coil | coils |
write_single_coil_request |
Write |
0x06 |
Write Single Register | holding-registers |
write_single_register_request |
Write |
0x07 |
Read Exception Status | diagnostics |
read_exception_status_request |
Read |
0x08 |
Diagnostics | diagnostics |
diagnostics_request |
R/W |
0x0B |
Get Comm Event Counter | diagnostics |
get_comm_event_counter_request |
Read |
0x0C |
Get Comm Event Log | diagnostics |
get_comm_event_log_request |
Read |
0x0F |
Write Multiple Coils | coils |
write_multiple_coils_request |
Write |
0x10 |
Write Multiple Registers | holding-registers |
write_multiple_registers_request |
Write |
0x11 |
Report Server ID | diagnostics |
report_server_id_request |
Read |
0x14 |
Read File Record | file-record |
read_file_record_request |
Read |
0x15 |
Write File Record | file-record |
write_file_record_request |
Write |
0x16 |
Mask Write Register | holding-registers |
mask_write_register_request |
Write |
0x17 |
Read/Write Multiple Registers | holding-registers |
read_write_multiple_registers_request |
R/W |
0x18 |
Read FIFO Queue | fifo |
read_fifo_queue_request |
Read |
0x2B / 0x0E |
Read Device Identification | diagnostics |
read_device_identification_request |
Read |
mbus-server receives FC 0x2B as Encapsulated Interface Transport and currently
routes only MEI 0x0E to the application callback. Other MEI types are rejected by the stack.
Most read-style callbacks write encoded payload bytes into an output buffer and return the number of bytes written:
fn read_...(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
address: u16,
quantity: u16,
out: &mut [u8],
) -> Result<u8, MbusError>;This applies to:
- FC01
read_coils_request - FC02
read_discrete_inputs_request - FC03
read_multiple_holding_registers_request - FC04
read_multiple_input_registers_request - FC18
read_fifo_queue_request - FC14
read_file_record_request - FC17
read_write_multiple_registers_requestfor the read portion
For coil and discrete-input reads, out contains packed bits. For register-style reads,
out contains big-endian u16 words.
Single-write callbacks mutate application state directly and return Result<(), MbusError>:
fn write_single_coil_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
address: u16,
value: bool,
) -> Result<(), MbusError>;
fn write_single_register_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
address: u16,
value: u16,
) -> Result<(), MbusError>;Multi-write callbacks receive already-decoded payloads:
fn write_multiple_coils_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
starting_address: u16,
quantity: u16,
values: &[u8],
) -> Result<(), MbusError>;
fn write_multiple_registers_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
starting_address: u16,
values: &[u16],
) -> Result<(), MbusError>;Additional write-capable callbacks:
fn mask_write_register_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
address: u16,
and_mask: u16,
or_mask: u16,
) -> Result<(), MbusError>;
fn write_file_record_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
file_number: u16,
record_number: u16,
record_length: u16,
record_data: &[u16],
) -> Result<(), MbusError>;ServerDiagnosticsHandler uses a few specialized return shapes:
fn read_exception_status_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
) -> Result<u8, MbusError>;
fn diagnostics_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
sub_function: DiagnosticSubFunction,
data: u16,
) -> Result<u16, MbusError>;
fn get_comm_event_counter_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
) -> Result<(u16, u16), MbusError>;
fn get_comm_event_log_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
out_events: &mut [u8],
) -> Result<(u16, u16, u16, u8), MbusError>;
fn report_server_id_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
out_server_id: &mut [u8],
) -> Result<(u8, u8), MbusError>;
fn read_device_identification_request(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
read_device_id_code: u8,
start_object_id: u8,
out: &mut [u8],
) -> Result<(u8, u8, bool, u8), MbusError>;With diagnostics-stats, the stack auto-handles the FC08 counter-oriented sub-functions:
| Sub-function | Name |
|---|---|
0x000A |
Clear Counters |
0x000B |
Bus Message Count |
0x000C |
Bus Comm Error Count |
0x000D |
Bus Exception Error Count |
0x000E |
Server Message Count |
0x000F |
Server No-Response Count |
0x0010 |
Server NAK Count |
0x0011 |
Server Busy Count |
0x0012 |
Bus Character Overrun Count |
0x0014 |
Clear Overrun Counter/Flag |
Other FC08 sub-functions continue to flow through diagnostics_request.
Serial broadcast writes are supported only when
ResilienceConfig::enable_broadcast_writes = true.
- Broadcast address is
0 - Only write-oriented requests are processed
- No response is sent
- TCP unit id
0is still discarded
Your callback can detect the case with uid.is_broadcast().
Returning Err(MbusError::...) causes the server to build a Modbus exception response and
then invoke ServerExceptionHandler::on_exception(...).
fn on_exception(
&mut self,
txn_id: u16,
uid: UnitIdOrSlaveAddr,
function_code: FunctionCode,
exception_code: ExceptionCode,
error: MbusError,
)Common outcomes are:
- unsupported or disabled handlers map to
IllegalFunction - invalid address windows map to
IllegalDataAddress - invalid quantities, values, or malformed sub-function payloads map to
IllegalDataValue - internal queue-pressure or transport-side failures surface as server-side exceptions
If you need exact per-service behavior, use the service modules in mbus-server/src/services as